Frequently asked questions
Fire protection boards
Aestuver® fire protection boards can be worked with standard tools available on the market – for example for sawing, drilling and fixing. No special tools are required, which makes installation on site much easier.
Because the components are easy to integrate and are delivered ready to install, switching over usually takes little effort and is easy to plan.
With the different types of Aestuver® fire protection board, all standard fire resistance classes from EI 30 to EI 240 can be achieved.
Through early, application-specific advice, we provide a customised product solution that is optimally matched to the fire protection system and the project requirements.
Through monitored production processes, documented quality controls and clearly defined manufacturing steps.
Cement-bonded fire protection boards remain stable and dimensionally stable under thermal load – for example in the event of fire.
Thanks to their high cement content, they have both a cooling and an insulating effect. At the same time, they are highly resistant to thermal deformation and cracking.
Aestuver® product lines have a European Technical Assessment (ETA), which is recognised in most European countries as proof of suitability for use. In principle, they can therefore be used in many European markets – however, project-specific requirements should be checked case by case.
Aestuver® fire protection boards are manufactured exclusively in Germany, at our factory in Calbe (Saale).
Aestuver® fire protection boards are suitable for all buildings that require high-quality structural fire protection. Our focus is on infrastructure, industry, commercial buildings and special structures, as well as on refurbishment, extensions and retrofits of existing buildings. With personal advice and in-house prefabrication, we are a strong partner for planners, distributors, contractors and industry.
Our technical advisers will be happy to help. You can find their contact details on our contact page.
Aestuver® fire protection boards are a cost-effective alternative to competing products in the segment of cement-bonded, moisture-resistant fire protection boards. Project-specific prices are available from specialist building materials retailers.
Yes. Their arc resistance has been verified by the Fraunhofer Institute in accordance with test specification DIN VDE 0303, Part 5.
As our cable ducts are made mainly from Aestuver® fire protection boards, they are generally weather-resistant. However, structural weather protection is still recommended to stop water getting into the ducts. Connecting profiles and supporting structures must also be protected against corrosion.
Cement-bonded Aestuver® fire protection boards have a hard, smooth, abrasion-resistant surface similar to fair-faced concrete. In the event of fire, they remain stable and keep their shape even at very high temperatures. They are also water-, frost- and mould-resistant – a combination of properties that gypsum-based products cannot offer.
Yes. According to ETA-11/0458, Aestuver® fire protection boards may also be installed outdoors in areas exposed to the weather.
Yes. Aestuver® fire protection boards are water- and frost-resistant, making them suitable for use in changing climatic conditions.
Aestuver® fire protection boards are available from building materials retailers in Germany, such as specialist dealers for drywall, insulation, roofing and insulation technology.
Depending on the construction, the boards are either fixed board-to-board with staples or screws, or mounted on a metal, timber or concrete substructure. Detailed recommendations on suitable fixings can be found on pages 106–107 of the Aestuver® manual.
According to the European Assessment Documents (EADs), there are four use categories:
Type X: indoors, partially exposed and fully exposed to the weather – the highest requirement level
Type Y: indoors and areas partially exposed to the weather (e.g. covered outdoor areas)
Type Z1: indoors with high humidity or fluctuating temperatures
Type Z2: indoors only, with constant climatic conditions
Aestuver® fire protection boards meet the highest category, Type X (EAD 350142-00-1106).
Coatings with commercially available dispersion-, silicate-, synthetic resin- or acrylic-based products are possible. A deep-penetrating primer is recommended. For skimming the surface, fermacell™ Powerpanel fine surface treatment is suitable in combination with full-surface reinforcement using fermacell™ HD reinforcing mesh. The fermacell™ HD render system is also approved. Application instructions can be found from page 103 of the Aestuver® manual.
Technically, Aestuver® fire protection boards can be used outdoors permanently without an additional coating. For aesthetic reasons, however, we recommend structural weather protection or a suitable coating. Exception: in road tunnels, a surface coating is required for frost and road-salt resistance. Detailed information can be found from page 103 of the Aestuver® fire protection manual.
D+2
In principle, no further accessories are required.
Sealing strips can be supplied as an option; they are fitted between the cable trough and the D+2 element to stop the elements rocking. Pre-assembled inspection aids are also available.
Yes – with a slip-resistant coating (R 13), Aestuver® D+2 elements can be used outdoors permanently.
We supply Aestuver® D+2 elements cut precisely to customer specifications.
Standard sizes go up to 1,250 × 625 mm; larger formats are available on request.
The load-bearing capacity depends on the span.
For small spans of up to 600 mm, for example, traffic loads of more than 10 kN/m² can be supported.
With a live load of 5 kN/m², the span can be up to 950 mm.
The weight per unit area is approximately 50 kg/m², so a cable trough cover measuring 700 × 600 mm, for example, weighs approximately 21 kg.
This combines low weight with high load-bearing capacity.
Aestuver®
Process, installation and defect-related costs in particular are significantly reduced, optimising total costs over the entire product life cycle.
Less installation work, reduced complexity and consistent quality lead to predictable costs and greater efficiency.
For projects with high fire safety requirements, complex components and series production that require safe, efficient implementation.
Components designed for easy integration simplify workflows and make production processes more efficient.
Yes. Aestuver® and fermacell® are brands of James Hardie Europe GmbH, headquartered in Düsseldorf.
Aestuver® FireShield
Yes, Aestuver® FireShield is also suitable for timber construction. The elements are usually delivered directly to the manufacturer of the timber ceiling elements, who installs the Aestuver® FireShield fire stop in the timber elements at the factory. This ensures reliable fire protection and fall protection in every phase of construction.
As the side wall of Aestuver® FireShield is made from a 25 mm fire protection board, additional lining of the opening is not needed in most cases. The elements are made to exact dimensions according to the opening plan; they are simply inserted into the opening and fixed at the sides in the reveal with screw anchors.
Special situations:
Cast timber-hybrid floor: Aestuver® FireShield is fixed to the formwork in the usual way and cast into the concrete – no additional mechanical fixing with screw anchors is required.
Timber-hybrid floor with concrete elements: Aestuver® FireShield is mechanically fixed to the sides of the timber structure; the concrete elements are joined to the sides of the element.
Timber floor: Aestuver® FireShield is delivered directly to the element manufacturer and installed there, or placed in the opening on site and mechanically fixed at the sides.
Yes, Aestuver® FireShield can be fitted into an existing opening. An Aestuver® FireShield partner company measures the opening on site; the element is then made to these exact dimensions, inserted into the existing opening and fixed at the sides with screw anchors.
No, there is no loss of space. The side wall of Aestuver® FireShield is 25 mm thick, and the space available between the reinforcement and the opening is 30 mm, so the element can be integrated without taking up extra space and the clear opening dimensions are retained.
The only exception is next to seismic walls: as the side wall of Aestuver® FireShield must not be cast into the load-bearing wall, the element is supplied with screw anchors, which are then cast into the wall.
No, specific design adjustments are not usually necessary. The spacing between services can be kept as with a conventional fire stop. However, given the low minimum clearances that have been verified, it may be worth revising the layout if you want to save space and use smaller shaft cross-sections.
The elements are usually ordered directly by the main contractor. Aestuver® always provides tender texts and specification extracts free of charge.
In principle, the site management decides when the openings in Aestuver® FireShield are made. However, the Aestuver® FireShield team recommends that the Aestuver® FireShield partner company only cuts the openings once the floor above has been concreted with its Aestuver® FireShield elements. This keeps the building watertight and allows building services installation to start promptly.
Both the openings in Aestuver® FireShield and the fire stops for these openings are made by a trained specialist company – giving you a clean, complete solution from a single source. As safety is our top priority, our partner companies attend refresher training every year so that they are always aware of the specific risks of working in riser zones.
Aestuver® FireShield elements are manufactured at our factory in Calbe (Saale), Germany, in accordance with the requirements of the aBG. The fire protection boards used for them are also produced there.
The elements are usually configured and manufactured according to the project’s opening plan. In addition to project-specific prefabrication, the following standard sizes are available: 625 × 625 mm, 1,250 × 625 mm and 1,250 × 2,600 mm. On request, we are also happy to develop a standard size with you for your typical construction method.
The Aestuver® FireShield elements are installed under the responsibility of the site foreman. As the foreman is in direct contact with the Aestuver® FireShield partner company, delivery dates and batch sizes are agreed jointly. The foreman then receives a numbered opening plan from the partner company, which clearly shows every element and its position.
Thanks to new penetration tests on Aestuver® FireShield, special fire-resistant rubber insulation is no longer needed, so services with continuous insulation can be routed directly through Aestuver® FireShield. Other fire protection components, such as fire protection collars for thermoplastic pipes up to 110 mm in diameter, are also no longer required. The Aestuver® FireShield cover plate provides fire protection to S90/EI90.
Using Aestuver® FireShield elements for openings in riser zones offers economic and practical advantages and speeds up building services installation. Because Aestuver® FireShield combines formwork, fire stop, fall protection and waterproofing in a single solution, lower storeys can already be fitted out while upper storeys are still at the shell construction stage. EI90 fire protection and fall protection with an approved surface load of 800 kg/m² are ensured throughout the construction phase, and once cast into concrete, Aestuver® FireShield is permanently watertight.
In addition, the tested minimum clearances between pipes – down to zero – allow more compact shaft planning, and the space saved brings clear financial benefits.
The largest standard element measures 2,600 × 1,250 mm. On request, custom sizes of up to 12,500 × 1,250 mm or 4,000 × 2,600 mm can be produced – Aestuver® FireShield is made to measure for each project.
Yes – with many benefits. Since the latest approvals were introduced, Aestuver® FireShield elements have increasingly been used in residential construction too. As well as removing the need for various fire protection components – such as special fire-resistant insulation or fire protection collars at penetrations – Aestuver® FireShield ensures continuous watertightness. This means building services installation can start before the shell construction of the upper floors is complete.
Aestuver® FireShield is also ideal for smaller openings, for example for individual service lines. The openings are made easily by an Aestuver® FireShield partner company and replace costly core drilling.