Special constructions

Bespoke fire protection solutions

Where standard solutions reach their limits, Aestuver® offers special constructions for structural fire protection. For complex geometries, unusual installation situations or specific fire protection requirements, Aestuver® develops bespoke constructions precisely tailored to the requirements of each project – meeting the highest standards of safety, functionality and cost-effectiveness.

Aestuver® fire protection boards provide certified system solutions for demanding applications in building construction, industry and infrastructure. We support your project from initial planning to successful completion and develop safe, technically sound and practical solutions even for complex requirements.

Fire protection for bonded reinforcement (walls/ceilings)

CFRP strips can be used as retrofitted bonded reinforcement to strengthen reinforced concrete components. In the event of fire, Aestuver® fire protection boards reliably protect these bonded strips from critical temperatures.

The required board thickness depends on the permissible temperature of the adhesive in the event of fire. The system, with fire protection boards in two or three layers, provides fire resistance of up to 120 minutes and can be used indoors and outdoors without additional coatings.

Technical specifications:

  • Fire resistance classes F 30-A to F 120-A

  • Verification: ETA-11/0458 and report GS 3.2/14-084-1

  • Board thicknesses from 15 mm to 50 mm

  • Design temperatures 40–90 °C

  • Board joints butt-jointed

  • Fixing with approved steel anchors in concrete

Fire protection upgrading of sprinkler supply and firefighting pipes

Aestuver® fire protection boards can be used to upgrade sprinkler and fire-extinguishing pipework to meet fire safety requirements and keep it working in the event of fire. The certified system ensures functional integrity for more than 90 minutes, contributing to the reliable operation of fire-extinguishing systems.

Technical specifications:

  • Protection objective: pipes used as sprinkler supply lines must be classified according to their fire resistance for the intended application

  • Fire protection upgrade: 40 mm Aestuver® fire protection board

  • Fire protection classification: functional integrity > 90 min

  • Fire protection certificate: GS 3.2/15-344-1

Heat protection behind wood-burning stoves

Aestuver® fire protection boards reliably protect against radiant heat behind wood-burning stoves and are suitable for continuous temperatures of up to 250 °C. For safe use, they must be installed with rear ventilation and all clearances and requirements must be met.

Please note when carrying out the work:

  • Rear-ventilated installation with a 25 mm gap

  • A minimum distance of 20 cm from the stove is recommended

  • Consult the stove manufacturer and the chimney sweep

  • Compliance with the German state building regulations (LBO) and the Model Firing Installations Ordinance (MFeuV) is mandatory